PRODUCT SERIES
YF-TP-HV3P
High-voltage three-phase hybrid inverter configurations in the 40–60kW range.

3Configurations
40–60 kWPower Range
200–300 VNominal Voltage Range
SERIES CONFIGURATIONS
Compare Configurations
Compare models in this series and choose a configuration for your inquiry.
Scroll horizontally to compare all models. Highlighted rows have different specifications.
| Parameter | ![]() | ![]() | ![]() |
|---|---|---|---|
| Inverter Input/Output(Grid) | |||
| Rated Power | 40 | 50 | 60 |
| Rated Voltage | 380/400VAC., 3W+N+PE | 380/400VAC., 3W+N+PE | 380/400VAC., 3W+N+PE |
| Rated Frequency | 50/60Hz | 50/60Hz | 50/60Hz |
| Power Factor Range | 0.8 leading ~ 0.8lagging | 0.8 leading ~ 0.8lagging | 0.8 leading ~ 0.8lagging |
| Max.Continuous Current(Input/Output) | 121.6A/60.8A | 152A/76A | 182.4A/91.2A |
| Max.Output Overcurrent Protection | 91.2A/86.6A | 114A/108.3A | 136.7A/129.9A |
| Battery | |||
| Battery Type | Lithium-ion/Lead-acid | Lithium-ion/Lead-acid | Lithium-ion/Lead-acid |
| Battery Voltage Range | 135V~850V | 135V~850V | 135V~850V |
| Rated Battery Voltage | 200V | 250V | 300V |
| Max. Charge Current | 2*100A | 2*100A | 2*100A |
| Max. Discharge Current | 2*100A | 2*100A | 2*100A |
| Reverse Connect Protection | Yes | Yes | Yes |
| PV Input | |||
| No.of MPPT Tracker/Strings | 4/2+2+2+2 | 4/2+2+2+2 | 4/2+2+2+2 |
| Max.PV Input Power | 80kW | 100kW | 100kW |
| Max.DC Voltage | 1000V | 1000V | 1000V |
| MPPT Voltage Range | 150V~850V | 150V~850V | 150V~850V |
| Start-up Voltage | 200V | 200V | 200V |
| Max.Input Current/sring | 8*20A | 8*20A | 8*20A |
| Isc PV (Absolute Maximum)/Sring | 8*30A | 8*30A | 8*30A |
| AC Output(EPS)/Generator | |||
| EPS Rated Output Voltage | 380/400VAC., 3W+N+PE | 380/400VAC., 3W+N+PE | 380/400VAC., 3W+N+PE |
| EPS Rated Output Frequency | 50/60Hz | 50/60Hz | 50/60Hz |
| EPS Rated Output Active Power | 40kW | 50kW | 60kW |
| EPS Rated Output Apparent Power | 40kVA | 50kVA | 60kVA |
| EPS Rated Output Current | 60.8A/57.7A | 76A/72.2A | 91.2A/86.6A |
| Overload Capacity (Off Grid) | 110% 30s/120% 10s/150% 0.2s | 110% 30s/120% 10s/150% 0.2s | 110% 30s/120% 10s/150% 0.2s |
| Efficiency | |||
| MPPT Efficiency | 99.90% | 99.90% | 99.90% |
| Euro-efficiency | 97.50% | 97.50% | 97.50% |
| Max. Efficiency | 98.50% | 98.50% | 98.50% |
| Protection & Feature | |||
| Insulation Monitoring | Yes | Yes | Yes |
| Residual Current Monitoring | Yes | Yes | Yes |
| Parallel Function | Yes, Up to 6 Pcs | Yes, Up to 6 Pcs | Yes, Up to 6 Pcs |
| Protection Degree | IP66 | IP66 | IP66 |
| Certifications | ENIEC 62477-1, ENIEC-62109-1/2, ENIEC 61000-6-2,EN50549-1/10, VDE-AR-N 4105 | ENIEC 62477-1, ENIEC-62109-1/2, ENIEC 61000-6-2,EN50549-1/10, VDE-AR-N 4105 | ENIEC 62477-1, ENIEC-62109-1/2, ENIEC 61000-6-2,EN50549-1/10, VDE-AR-N 4105 |
| Other Protection | Ground fault current monitoring, Earth fault detection, Residual current(RCD)Detection etc. | Ground fault current monitoring, Earth fault detection, Residual current(RCD)Detection etc. | Ground fault current monitoring, Earth fault detection, Residual current(RCD)Detection etc. |
| General Parameter | |||
| Storage Temperature Operating Temperature | -25°C~+60°C -25°C~+60°C(Linely derating to 60% when exceed +45°C~+60°C) | -25°C~+60°C -25°C~+60°C(Linely derating to 60% when exceed +45°C~+60°C) | -25°C~+60°C -25°C~+60°C(Linely derating to 60% when exceed +45°C~+60°C) |
| Humidity | 0%~100%(Non-condensing) | 0%~100%(Non-condensing) | 0%~100%(Non-condensing) |
| Max. Operating Altitude | 4000m | 4000m | 4000m |
| Noise | <65dB | <65dB | <65dB |
| Machine Dimensions(W*H*D) | 544*880*278mm | 544*880*278mm | 544*880*278mm |
| Machine Weight(Net Weight) | 88kg | 88kg | 88kg |
| Display & Communication | |||
| Display | App+LED/ LCD (-S version) | App+LED/ LCD (-S version) | App+LED/ LCD (-S version) |
| Interface | RS485/WiFi/CAN/DRM(Optional: Bluetooth/LAN/Meter) | RS485/WiFi/CAN/DRM(Optional: Bluetooth/LAN/Meter) | RS485/WiFi/CAN/DRM(Optional: Bluetooth/LAN/Meter) |
| Documents & Test Conditions | Datasheet ↗Manual ↗*Test conditions: 0.5C charge/discharge, @25°C, 80% DOD; product specifications are subject to change without prior notice. | Datasheet ↗Manual ↗*Test conditions: 0.5C charge/discharge, @25°C, 80% DOD; product specifications are subject to change without prior notice. | Datasheet ↗Manual ↗*Test conditions: 0.5C charge/discharge, @25°C, 80% DOD; product specifications are subject to change without prior notice. |
Specifications and test conditions apply to the corresponding configuration. Refer to its datasheet for details.