Get a Quote ↗

PRODUCT SERIES

YF-LV-P3E 8–12kW

Three-phase low-voltage hybrid inverter configurations for 48V battery systems.

YF-LV-P3E 8–12kW
3Configurations
8–12 kWPower Range
48 VNominal Voltage Range

SERIES CONFIGURATIONS

Compare Configurations

Compare models in this series and choose a configuration for your inquiry.

Scroll horizontally to compare all models. Highlighted rows have different specifications.

Technical specifications by configuration
Parameter
YF-LV-P3E-8048
YF-LV-P3E-8048
YF-LV-P3E-10048
YF-LV-P3E-10048
YF-LV-P3E-12048
YF-LV-P3E-12048
Battery Input Data
Battery TypeLithium or lead-acid batteryLithium or lead-acid batteryLithium or lead-acid battery
Rated Battery Voltage48V48V48V
Maximum Charging Voltage≤60V(Configurable)≤60V(Configurable)≤60V(Configurable)
Maximum Charge/discharge Current190A210A250A
PV Input Data
Maximum DC Input Power16000W20000W24000W
Maximum DC Input Voltage1000V1000V1000V
MPPT Operating Voltage Range200V~800V200V~800V200V~800V
Starting Voltage150V150V150V
Maximum Input Current18/18A36/18A36/18A
MPPT Number222
AC Output Parameters(ON-GRID)
Maximum Output Apparent Power8800W11000W13200W
Rated Output Voltage380/400V380/400V380/400V
Rated Output Frequency50 Hz/60 Hz50 Hz/60 Hz50 Hz/60 Hz
Max. Output Current13.3A16.7A20A
Output Power Factor1(-0.8 leading~+0.8lagging)1(-0.8 leading~+0.8lagging)1(-0.8 leading~+0.8lagging)
AC Output Parameters(OFF-GRID)
Rated Output Apparent Power8000W10000W12000W
Maximum Output Apparent Power>200%, 15sec>200%, 15sec>200%, 15sec
Rated Output Voltage380/400V380/400V380/400V
Rated Output Frequency50 Hz/60 Hz50 Hz/60 Hz50 Hz/60 Hz
Max. Output Current13.3A16.7A20A
Efficiency
MPPT. Efficiency98%98%98%
Max. Efficiency94.5%94.5%94.5%
Europe Efficiency97.5%97.5%97.5%
Protection
PV Input Reverse Polarity ProtectionYesYesYes
PV Insulation Resistance DetectionYesYesYes
Residual Current DetectionYesYesYes
Output Over Current ProtectionYesYesYes
Output Short Circuit ProtectionYesYesYes
Output Over Voltage ProtectionYesYesYes
Basic Data
Parallel InterfaceMAX. 8 units in parallelMAX. 8 units in parallelMAX. 8 units in parallel
Operation Temperature-25°C~60°C(Frequency-decreasing above 45°C)-25°C~60°C(Frequency-decreasing above 45°C)-25°C~60°C(Frequency-decreasing above 45°C)
Storage Temperature-30°C~65°C-30°C~65°C-30°C~65°C
Relative Humidity0~95%0~95%0~95%
Working Altitude≤4000m(Frequency-decreasing above 2000m)≤4000m(Frequency-decreasing above 2000m)≤4000m(Frequency-decreasing above 2000m)
CoolingIntelligent Forced Air CoolingIntelligent Forced Air CoolingIntelligent Forced Air Cooling
Noise<55dB<55dB<55dB
Weight38kg38kg38kg
Dimensions (W*H*D)475*683*256mm475*683*256mm475*683*256mm
Protection ClassIP66IP66IP66
TopologyHF Isolation(Battery Side)HF Isolation(Battery Side)HF Isolation(Battery Side)
Standard
Safety Standard/EMC StandardNBIT32004-2018, IEC62109, IEC61000, IS16169 &IS16221(BIS)NBIT32004-2018, IEC62109, IEC61000, IS16169 &IS16221(BIS)NBIT32004-2018, IEC62109, IEC61000, IS16169 &IS16221(BIS)
Grid-connected StandardIEC61727, EN50549-1, VDE-4105, NRS-097-2-1, OVE-Richtlinie R25, UNE217001/2, Ordinace No.140IEC61727, EN50549-1, VDE-4105, NRS-097-2-1, OVE-Richtlinie R25, UNE217001/2, Ordinace No.140IEC61727, EN50549-1, VDE-4105, NRS-097-2-1, OVE-Richtlinie R25, UNE217001/2, Ordinace No.140
Other StandardIEC61683, IEC62116, EN50530, IEC60068IEC61683, IEC62116, EN50530, IEC60068IEC61683, IEC62116, EN50530, IEC60068
Documents & Test ConditionsDatasheet ↗*Test conditions: 0.5C charge/discharge, @25°C, 80% DOD; product specifications are subject to change without prior notice.Datasheet ↗*Test conditions: 0.5C charge/discharge, @25°C, 80% DOD; product specifications are subject to change without prior notice.Datasheet ↗*Test conditions: 0.5C charge/discharge, @25°C, 80% DOD; product specifications are subject to change without prior notice.

Specifications and test conditions apply to the corresponding configuration. Refer to its datasheet for details.